Description
Main
Range of product Modicon Quantum automation platform
Product or component type Dc discrete output module
Discrete output number 32
Complementary
Group of channels 4 groups of 8
Discrete output logic Positive logic (source)
Addressing requirement 2 output words
Discrete output voltage 24 V DC
Output voltage limits 19.2…30 V
Absolute maximum output 56 V for 1.3 s decaying pulse
Maximum voltage drop <0.4 V 0.5 A
Maximum load current 16 A per module
4 A per group
Surge current 5 A for 0.0005 s
Response time <= 1 ms at state 0 to state 1
<= 1 ms at state 1 to state 0
Maximum leakage current 0.4 mA 30 V
Load inductance Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz))) 50 Hz
Fault indication Blown fuse
Loss of field power
Associated fuse rating 3 A each point
5 A per group
Isolation between channels and bus 1780 Vrms DC for 1 minute
Isolation between group 500 Vrms DC for 1 minute
Protection type Internal output protection by 5 A fuse per group
Power dissipation 1.75 W + (0.4 V x total module load current)
Marking CE
Local signalling 1 LED (green)bus communication is present (Active):